Fil UL TC-ER (XHH/XHHW-2)

Fil UL TC-ER (XHH/XHHW-2)
Detay yo:
UL sètifye, lavi sèvis long
Plis pase 20 ane eksperyans nan pwodiksyon
Quick quote sou entènèt ak echantiyon gratis ki disponib
Voye rechèch
Rale dosye
Deskripsyon
Paramèt teknik
Sètifikasyon
TC-ER Cable

 

 
Fil UL TC-ER (XHH/XHHW-2)

● Kondiktè: Uncoated mou kwiv pa ASTM B-3. Gwosè ki pi piti pase #8 yo se konpresyon-bloke dapre ASTM B-8. Gwosè #8 ak pi gwo yo se kontra enfòmèl ant bloke dapre ASTM B-496.

● Izolasyon: Okonite-FMR satisfè oswa depase kondisyon izolasyon UL 1581, ICEA S-73-532 (NEMA WC57), ak ICEA S-95-658 NEMA WC70 Kalite II.

● Kodaj Koulè: Koulè debaz ak trasè jan yo montre sou do Fèy Done a, ak pou gwosè #8 AWG ak pi gwo, kondiktè nwa ak enprime nimewo sifas pa ICEA S-73-532 NEMA/WC57 Metòd 4.

● Kondiktè Grounding: Kote sa endike, fè oswa vèt izole kòb kwiv mete pa ASTM B-8 pou gwosè #8 AWG ak pi piti, wonn kontra enfòmèl ant pou gwosè ki pi gwo pase #8 AWG pou chak ASTM B-496 ak anba tab NEC. 250.122.

● Asanble: Kondiktè yo kab swiv UL 1277 lè l sèvi avèk file, jan sa nesesè, ak yon kasèt kab an jeneral.

● An jeneral jakèt: Konfòme ak UL 1277. Konpoze Okolon TS-CPE satisfè oswa depase kondisyon UL 1581.

 

Aplikasyon

 

 

Kab plato TC-ER pèmèt pou itilize sou kouran, ekleraj, kontwòl, ak sikui siyal; andedan kay la oswa deyò; nan plato kab, kous, antèman dirèk nan tè a, oswa kote sipòte nan kote deyò pa yon fil mesaje; pou sikui Klas 1 jan yo pèmèt nan
Atik 725 NEC a; ak nan plato kab nan Klas I, Divizyon 2 kote danjere nan etablisman endistriyèl kote kondisyon yo
nan antretyen ak sipèvizyon asire ke sèlman moun ki kalifye pral sèvis enstalasyon an.
Kab ki make TC-ER yo ka itilize tou ant yon plato kab ak ekipman itilizasyon oswa aparèy lè yo enstale an akò.
ak NEC 336.10(7).

flat cable application

 

Karakteristik

 

TC-ER

 

TC-ER (Tray Cable - Exposed Installation) kab te pase tès ignifuge plato vètikal IEEE 383-1974 ak 1202/FT4, osi byen ke estanda ignifuge flanm dife segondè entansite (210,000 BTU). /hr.) nan UL 1277 ak ICEA T-29-520, ki montre ekselan rezistans dife. Kalite kondiktè izole li yo gen ladan XHH/XHHW-2 ak cUL-rated RW75/RW90, ki ka kenbe pèfòmans ekselan nan tanperati ki ba anpil nan -40 degre, ak tanperati enstalasyon ki pi ba a ka rive nan -35 degre, bay yon solisyon pratik pou aplikasyon nan rejyon frèt.

 

Sètifikasyon

 

TC-ER Wire (Tray Cable - Exposed Run) kab sètifye UL, ki vle di ke yo te teste pwodwi a sevè epi li satisfè kondisyon ki nan Kòd fil elektrik Nò Ameriken an (NEC), epi asire sekirite nan anviwònman ekspoze.

Câbles TC-ER yo dwe sibi tès durability, tès fleksibilite, tès pèfòmans mekanik, ak lòt tès anvan yo ka jwenn sètifikasyon UL, bay itilizatè yo ak segondè-sekirite ak pwodwi kab serye epi redwi risk pou yo aksidan.

TC-ER cable certification

 

Pake

 

TC-ER cable package

 

Liy Pwodiksyon

 

TC-ER cable factory

 

Faktori kab avanse Greater Wire manifakti a gen yon anviwònman manifakti entelijan ak dijital. Atravè entegrasyon an san pwoblèm nan teknoloji dènye kri, faktori a avèk siksè elimine erè ak domaj ki ka rive nan pwosesis tradisyonèl asanble manyèl la. Chanjman nan fabrikasyon dijital la non sèlman ogmante efikasite, men tou demontre angajman nou pou bay kliyan nou yo pwodwi ki gen plis fyab. Kad faktori entelijan an asire yon pwosesis pwodiksyon rasyonalize ak san erè, minimize posiblite pou divèjans ki gen rapò ak moun ak ogmante presizyon ki te deja pa ka atenn. Mekanis enspeksyon egzat ak otomatik, faktori a estrikteman respekte kontwòl kalite. Pwodwi yo byen enspekte depi nan konmansman an nan etap final la nan pwosesis fabrikasyon an. Yo itilize deteksyon dijital imaj entèlijan ak teknoloji lazè pou asire ke chak pwodwi satisfè nòm strik yo fikse pa konpayi nou an. Angajman sa a nan bon jan kalite pwolonje nan presizyon enspeksyon nou an, ak ekipman pwodiksyon otomatik reyalize yon presizyon enpresyonan nan 0.002 mm, depase referans endistri yo.

 

kliyan

 

wire and cable company

 

 

Patnè

 

greater wire Partner

 

FAQ

 

 

 

 

K: Ki non konplè TC-ER kab?

A: Non konplè a se Tray Cable - Exposed Run, ki kab la apwopriye pou mete plato epi yo ka ekspoze dirèkteman pou enstalasyon.

K: Ki karakteristik dirab fil TC-ER?

A: Li se rezistan a lwil oliv, reyon UV, pwodwi chimik, enpak, ak etann.

K: Èske fil TC-ER enpèmeyab?

A: Wi, anpil câbles TC-ER yo enpèmeyab, men li depann de modèl la kab ak materyèl jakèt.

 

 

Baj popilè: ul tc-er fil (xhh/xhhw-2), Lachin ul tc-er fil (xhh/xhhw-2) manifaktirè, founisè, faktori

TC-ER cable

 

 

Gwosè kondiktè
AWG/kcmil
Kantite kondiktè
UL TC TIP
Epesè izolasyon - mils
Epesè jakèt - mils
Epesè jakèt - mm
Apeprè. OD - Pous
Apeprè OD - mm
Seksyon kwa
Zòn (pous kare)
Apeprè. Pwa nèt
lbs./1000'
Apeprè. Pwa bato
lbs./1000'
90 degre mouye oswa sèk
Anpasite NEC (1)*
75 degre mouye
Ampasite NEC
14(7X)
2 TC 30 45 1.14 0.39 9.8 0.12 95 115 15 15
3 TC-ER 45 1.14 0.41 10.3 0.13 115 135 15 15
4 TC-ER 45 1.14 0.44 11.3 0.15 140 160 15 15
5 TC-ER 45 1.14 0.48 12.2 0.18 165 185 15 15
7 TC-ER 45 1.14 0.52 13.3 0.21 200 220 15 14
9 TC-ER 60 1.52 0.64 16.2 0.32 290 310 15 14
12 TC-ER 60 1.52 0.71 18.1 0.40 370 390 12 10
19 TC-ER 60 1.52 0.83 21.0 0.54 510 530 12 10
37 TC-ER 80 2.03 1.14 29.1 0.03 985 1005 10 8
12(7X) 2 TC 30 45 1.14 0.42 10.7 0.14 120 140 20 20
3 TC-ER 45 1.14 0.45 11.3 0.16 145 165 20 20
4 TC-ER 45 1.14 0.49 12.4 0.19 180 200 20 20
5 TC-ER 45 1.14 0.53 13.5 0.22 220 240 20 20
7 TC-ER 60 1.52 0.61 15.5 0.29 295 315 20 17
9 TC-ER 60 1.52 0.70 17.9 0.39 390 410 20 17
12 TC-ER 60 1.52 0.79 20.0 0.49 500 520 15 12
19 TC-ER 80 2.03 0.96 24.4 0.72 745 765 15 12
37 TC-ER 80 2.03 1.27 32.3 1.27 1355 1375 12 10
10(7X)
2 TC 30 45 1.14 0.47 11.9 0.17 160 180 30 30
3 TC-ER 45 1.14 0.50 12.7 0.19 200 220 30 30
4 TC-ER 60 1.52 0.58 14.6 0.26 270 290 30 28
5 TC-ER 60 1.52 0.63 15.9 0.31 325 345 30 28
7 TC-ER 60 1.52 0.68 17.3 0.36 405 425 28 24
9 TC-ER 60 1.52 0.79 20.1 0.49 540 560 28 24
12 TC-ER 80 2.03 0.93 23.6 0.68 745 765 20 17
Ekipman Grounding Kondiktè: Nenpòt kondiktè nan TC rated câbles ka pou tout tan re-idantifye pandan enstalasyon kòm kondiktè a tè ekipman an akò ak Seksyon 250.119 (B) nan NEC la.
† Zòn transvèsal pou kalkil ranpli plato kab an akò ak Seksyon 392.22 NEC la.
 
(1) Anpasite
Anpasite yo baze sou Tablo 310.16 nan Kòd Elektrik Nasyonal pou kondiktè 90 degre sa yo nan yon tanperati anbyen 30 degre. Yo bay kolòn mouye 75 degre pou plis fòmasyon.
Anpasite yo montre yo aplike nan kous louvri nan kab, enstalasyon nan nenpòt kous ki apwouve, antèman dirèk sou tè a, oswa kòm kab ayeryen sou yon mesaje. Derating pou plis pase twa kondiktè ki pote kouran nan yon kous se an akò ak NEC Seksyon 310.15(C)(1).
Anpasite yo montre yo aplike tou pou câbles ki enstale nan plato kab an akò ak NEC Seksyon 392.80.
 
*Kouye a limite a 15, 20 ak 30 ampè pou chak Seksyon 240.4(D) NEC pou #14, #12 ak #10 AWG, respektivman.
 
Gwosè kondiktè AWG/kcmil UL TC TIP Kantite kondiktè Epesè izolasyon - mils Kondiktè tè AWG* Epesè jakèt - mils Epesè jakèt - mm Apeprè. OD - Pous Apeprè OD - mm
Seksyon kwa
Zòn (pous kare)
Apeprè. Pwa nèt
lbs./1000'
Apeprè. Pwa bato
lbs./1000'
90 degre mouye oswa sèk
Anpasite NEC (1)*
75 degre mouye
Anpasite NEC (1)
8(7X)
TC-ER
3 45 - 60 1.52 0.65 16.5 0.33 323 346 55 50
3 10* 60 1.52 0.68 17.3 0.36 396 419 55 50
4 - 60 1.52 0.71 18.0 0.40 414 443 45 40
4 10* 60 1.52 0.71 18.0 0.40 443 472 45 40
6(7X) TC-ER 3 45 - 60 1.52 0.73 18.5 0.42 448 477 75 65
3 8* 60 1.52 0.73 18.5 0.42 536 565 75 65
4 - 60 1.52 0.80 20.3 0.50 565 594 60 52
4 8* 60 1.52 0.82 20.3 0.50 662 697 60 52
4(7X)
TC
3 45 - 60 1.52 0.82 21.8 0.53 633 668 95 85
TC-ER
3 8* 60 1.52 0.82 21.8 0.53 732 767 95 85
TC
4 - 80 2.03 0.94 23.9 0.69 851 904 76 68
TC-ER
4 8* 80 2.03 0.95 24.1 0.71 936 989 76 68
2(7X)
TC 3 45 - 80 2.03 0.98 24.9 0.75 994 1063 130 115
TC-ER 3 6 80 2.03 0.98 24.9 0.75 1145 1214 130 115
TC 4 - 80 2.03 1.08 27.4 0.92 1227 1307 104 92
TC-ER 4 6 80 2.03 1.08 27.4 0.92 1276 1356 104 92
1(19X)
TC 3 55 - 80 2.03 1.09 27.7 0.93 1226 1338 150 130
TC-ER 3 6 80 2.03 1.09 27.7 0.93 1398 1478 150 130
TC 4 - 80 2.03 1.20 30.5 1.13 1582 1694 120 104
TC-ER 4 6 80 2.03 1.21 30.7 1.15 1662 1787 120 104
1/0(19X)
TC 3 55 - 80 2.03 1.17 29.7 1.08 1501 1615 170 150
TC-ER 3 6 80 2.03 1.17 29.7 1.08 1680 1805 170 150
TC 4 - 80 2.03 1.29 32.8 1.31 1917 2059 136 120
TC-ER 4 6 80 2.03 1.29 32.8 1.31 1986 2128 136 120
2/0(19X)
TC 3 55 - 80 2.03 1.26 30.0 1.25 1812 1954 195 175
TC-ER 3 6 80 2.03 1.26 30.0 1.25 2017 2159 195 175
TC 4 - 80 2.03 1.39 35.3 1.52 2356 2508 156 140
TC-ER 4 6 80 2.03 1.39 35.3 1.52 2420 2607 156 140
4/0(19X)
TC 3 55 - 80 2.03 1.48 37.6 - 2697 2884 260 230
TC-ER 3 4 80 2.03 1.49 37.8 - 2903 3090 260 230
TC 4 - 80 2.03 1.63 41.4 - 3466 3717 208 184
TC-ER 4 4 80 2.03 1.63 41.4 - 3564 4815 208 184
250(37X)
TC 3 65 - 80 2.03 1.62 41.1 - 2952 3095 290 255
TC-ER 3 4 80 2.03 1.62 41.1 - 3082 3259 290 255
TC 4 -
110
2.79
1.86 47.2 - 3965 4231 232 185
TC-ER 4 4 110 2.79 1.86 47.2 - 4093 4359 232 185
350(37X)
TC 3 65 - 110 2.79 1.89 48.0 - 4104 4370 350 310
TC-ER 3 3 110 2.79 1.89 48.0 - 4207 4536 350 310
TC 4 - 110 2.79 2.08 52.8 - 5334 5681 280 248
TC-ER 4 3 110 2.79 2.08 52.8 - 5494 5841 280 248
500(37X)
TC 3 65 - 110 2.79 2.14 54.4 - 5658 6005 430 380
TC-ER 3 2 110 2.79 2.14 54.4 - 5861 6208 430 380
TC 4 - 110 2.79 2.37 60.2 - 7352 7911 344 304
TC-ER 4 2 110 2.79 2.37 60.2 - 7560 8119 344 304
750(61X)
TC 3 80 - 110 2.79 2.57 65.3 - 8331 8958 535 475
TC-ER 3 1 110 2.79 2.57 65.3 - 8603 9930 535 475
TC 4 - 140
3.56
2.91 73.9 - 11080 11842 428 380
TC-ER 4 1 140
3.56
2.91 73.9 - 11343 12105 428 380
1000(61X)
TC 3 80 - 140 3.56 2.94 74.4 - 11078 11840 615 345
TC-ER 3 1 140 3.56 2.94 74.4 - 11463 12396 615 345
TC 4 - 140 3.56 3.26 82.8 - 14455 15388 492 430
TC-ER 4 1 140 3.56 3.26 82.8 - 14894 15827 492 430

 

Voye rechèch